STP FOAM FIRE RESIST 2-IN-1

Fire resistant foam without isocyanate.

Mono component foam which expands and hardens with ambient humidity. This foam does not contain isocyanate. Professional quality, Specially convenient for static joints in building constructions which have to resist fire up till 4 hours.

The aerosol has a remarkable valve system that allows manual application as well as the use of an application gun.

Description

General description                                                                                                           

Mono component foam which expands and hardens with ambient humidity. This foam does not contain isocyanate. Professional quality, Specially convenient for static joints in building constructions which have to resist fire up till 4 hours.

The aerosol has a remarkable valve system that allows manual application as well as the use of an application gun.

 

Features

  • 0 % isocyanantes.(well below the target stipulated by directive EU 67/548/CE).
  • Appropriate for sealing, insulating, filling and
  • Excellent adhesion to all common construction
  • Conform to the new European standards EN 1366-4 end the arrest of 22 March 2004 from the French Ministry of Internal
  • Fire class certified according report N°12-A-720 & 12-A-739 from Efectis according standard EN 13501-2. (see test report, available on simple request).
    • Resist fire up to 4
    • Seals smoke and gas.
  • Manual application for the filling of
  • The aerosol fits on an application gun for precise dosing

 

Applications

Filling of all kind of cavities in a building construction. Insulation of conduits.

Thermal and acoustic insulations Fixation of building components. Modeling.

 

Directions

Manual use:

  • Shake
  • Click/turn the manual dispensing tube with trigger, on the valve: place the wings against the openings on the valve. While pushing slightly, turn a quarter turn. Press short to position the tube well on the
  • Humidify the surfaces to be treated
  • Hold the can upside down. Place a finger on the trigger on each side of the dispensing tube and activate by pressing the trigger straight down (do not tilt).

 

Use with the application gun:

  • Shake
  • Screw the aerosol on the
  • Humidify the surfaces to be treated
  • Regulate the flow rate with the throttling nut on the
  • After removal of an empty aerosol, clean the gun with CRC PU Foam

Note: Clean spoilage of non cured product immediately with CRC PU Foam Cleaner. Cured product only allows mechanical removal.

A safety data sheet (MSDS) according to EU directive 91/155/EEC and amendments is available for all CRC products.

 

 

Typical product data (without propellant)                                                                                               

Color                                                                      : grey

Fire reaction class                                                  : EN 1666-4                            DIN 4102-1

Ambient application temperature                         : 0°C to +35°C

Maximal gap filling                                                : 50%

Drying time                                                            :  to touch 10 min                    FEICA TM 1014

to be cut 60 min                   FEICA TM 1005

full curing : 24 hours

Expanded volume                                                  :  a 500 ml aerosol produces    FEICA TM 1003

8 liters when applied   manual or with a gun

Thermal conductivity                                             : 0,036 W/m.K                        EN 12667

Tensile strength                                                      : 25 kPa                                  ISO 527

Elongation at break                                                : 20 %                                     ISO 527

Temperature resistance                                          : permanent -20°C to +90°C temporarily -20°C to 130°C

Conservation and storage                                      : At a temperature between 5°C and 25°C Straight up, 9 months in                                                                                    the original closed packaging in a fresh and dry environment.

 

Packaging

Aerosol              12×500 ML

All statements in this publication are based on service experience and/or laboratory testing. Because of the wide variety of equipment and conditions and the unpredictable human factors involved, we recommend that our products be tested on-the-job prior to use. All information is given in good faith but without warranty neither expressed nor implied. This Technical Data Sheet may already have been revised at this moment for reason such as legislation, availability of components and newly acquired experiences. The latest and only valid version of this Technical Data Sheet will be sent to you upon simple request or can be found on our website: www.crcind.com. We recommend you to register on this website for this product so you will be able to receive any future updated version automatically.